This premises was found to be in compliance with the Health Protection and Promotion Act R.S.O. 1990.
This premises was found to be in compliance with the Health Protection and Promotion Act R.S.O. 1990.
Corrected During Inspection
Non-critical
Facility completes weekly or monthly tests as required.
- Inspect all water, gravity and suction outlet covers at least once within each period of 30 operating days.
- Test-buttons associated with the ground current leakage detecting and de-energizing devices are activated daily, and tested either monthly or in accordance with manufacturer's directions, whichever is more frequent.
This premises was found to be in compliance with the Health Protection and Promotion Act R.S.O. 1990.
Corrected During Inspection
Non-critical
Facility completes daily records as required.
- Record the estimated number of bather uses during the operating day.
This premises was found to be in compliance with the Health Protection and Promotion Act R.S.O. 1990.
This premises was found to be in compliance with the Health Protection and Promotion Act R.S.O. 1990.
This premises was found to be in compliance with the Health Protection and Promotion Act R.S.O. 1990.
Corrected During Inspection
Non-critical
Water meter & make-up water requirements are met.
- Ensure make-up water is added to the pool during each operating day in a minimum amount of 15 litres per bather.
Contact Us
